Description
Input Voltage | 24 VAC, 50/60 Hz, 1.25W |
Control Signal | ±10 VDC control signal from a 5024(e) or 5084e controller |
Output Voltage | 0-18 kVDC, ±10% for each polarity; positive and negative output levels adjusted centrally at controller and locally at each emitter |
Output Current | <15 mA; current and voltage limited to eliminate shock hazard |
Connectors | Telephone type RJ-11 modular jack receptacle on each end of emitter |
Output Control | Each emitter has controls that independently adjust both positive and negative output |
Regulation | Output and balance stability is achieved by independently regulating the ion emission voltage of each polarity at each emitter |
Timing | Precise timing (0-10 sec) is supplied by the controller. LEDs on each emitter indicate the polarity of the ion emission |
Ion Emission | Pulsed DC |
Emitter Points | Single crystal silicon, machined titanium, or tungsten alloy; all emitter points are replaceable; estimated emitter point life varies from 2-3 years depending on material used |
Calibration | Annually, semi-annually, or quarterly depending on manufacturing sensitivity |
Ozone | <0.005 ppm |
EMI | Below background level |
Alarm | Visual alarm, red LED located in the middle of the emitter chassis indicates an alarm condition; audible alarm, sounds at the 5024e/5084e controller when an alarm event occurs at any emitter |
Mounting | A variety of surface and flush mounting methods and brackets is available, including cleanroom-compatible interlocking self-adhesive mounts (3M TYPE SJ 3551) |
Emitter Rods | Available in 2.5, 5, 10, 15, 24, 36, or 60 in. lengths (63.5, 127, 254, 381, 609, 914, 1524 mm) |
Dimensions | 1.25H x1.5D x 17.5L in. (3.2 x 3.8 x 44.5 cm) |
Weight | 1.4 lb (0.5 kg) |
Components Required | Model 5024(e) or 5084(e) Controller |
Warranty | 2 year limited warranty |